Which countermeasures are necessary to prevent the creation of an ATEX area around the electrolyser?

Technical rooms where Enapter electrolysers are installed, shall be maintained Safe (i.e. Non-hazardous) according to IEC60079-10-1, by proper ventilation systems (i. e. with adequate dilution rate). Hydrogen sensor installation is highly recommended to detect any potential leaks and immediately stop

January 11, 2022

Technical rooms where Enapter electrolysers are installed, shall be maintained Safe (i.e. Non-hazardous) according to IEC60079-10-1, by proper ventilation systems (i. e. with adequate dilution rate). Hydrogen sensor installation is highly recommended to detect any potential leaks and immediately stop H2 production. Enapter Electrolysers are technically leak-tight by design, nevertheless acc. to IEC60079-10-1, they shall be considered a potential source of secondary release grade (i.e. not expected during normal operation of the equipment) for assessment of the ventilation.